When you see it… (Bollards)

Bollard

How many code/RAGAGEP violations can you identify?

Tip: Code(s) and RAGAGEPs require equipment to be protected against contact with mobile equipment when that contact could lead to an LOPC event involving a hazardous material.

Bollard

Answer(s) below:

SECTION 312

VEHICLE IMPACT PROTECTION

312.1 General. Vehicle impact protection required by this code shall be provided by posts that comply with Section 312.2 or by other approved physical barriers that comply
with Section 312.3.

312.2 Posts.

Guard postS shall comply with ALL of the following requirements:

1. Constructed of steel not less than 4 inches (102 mm) in diameter and concrete filled.

2. Spaced not more than 4 feet (1219 mm) between posts on center.

3. Set not less than 3 feet (914 mm) deep in a concrete footing of not less than a 15-inch (381 mm) diameter.

4. Set with the top of the posts not less than 3 feet (914 mm) above ground.

5. Located not less than 3 feet (914 mm) from the protected object.

 

312.3 Other barriers.

Barriers, other than posts specified in Section 312.2, that are designed to resist, deflect or visually deter vehicular impact commensurate with an anticipated impact scenario shall be permitted where approved.