Pressure Testing gone bad (Sprinkler Pipe)

On March 9, 2009, Employee #1 was testing a newly-installed 6 in. steel fire protection water main. When it was pressurized with air, a 6 in. pipe cap flew off the end of the pipe and struck Employee #1’s forehead, killing him.

Violations/PenaltiesSeriousTotal
Initial Violations55
Current Violations33
Initial Penalty$13,550$13,550
Current Penalty$5,175$5,175
FTA Penalty$0$0
#Citation IDCitaton TypeStandard CitedIssuance DateAbatement Due DateCurrent PenaltyInitial PenaltyFTA PenaltyContestLatest EventNote
1.01001Serious5A000106/17/200906/29/2009$0$4,900$006/26/2009F – Formal SettlementCitation has been deleted.
2.01002Serious19260020 B0106/17/200910/26/2009$750$750$0F – Formal Settlement 
3.01003Serious19260021 B0206/17/200910/26/2009$3,675$4,900$006/26/2009F – Formal Settlement 
4.01004Serious19260100 A06/17/200906/29/2009$0$1,500$006/26/2009F – Formal SettlementCitation has been deleted.
5.01005ASerious19260404 F07 IVC06/17/200906/29/2009$750$750$0F – Formal Settlement 
6.01005BSerious19260405 G02 IV06/17/200906/29/2009$0$750$006/26/2009F – Formal Settlement 

Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the hazard of being struck by an unsecured plumbing end cap when performing pressure testing.

(a) Building # 2-1361, basement level, Fort Bragg, North Carolina:

On or about March 9, 2009, a 6 inch steel cap, with mechanical flanges, became disconnected, and became a projectile, while compressed air was used to test the piping system for leaks. Among others, a feasible and useful method of abatement would be to ensure the cap is secured prior to testing such as by following industry best practices by use of threaded rods and floor anchors or other approved restraint devices.

Source: https://www.osha.gov/ords/imis/establishment.inspection_detail?id=311093728