Poor Design and Failure to Test Dust Collection System Among Causes of Flash Fire that Burned Seven Workers in 2012 (CSB)

The flash fire that burned seven workers, one seriously, in 2012 resulted from the accumulation of combustible dust inside a poorly designed dust collection system that had been put into operation only four days before the accident.  The CSB  investigation team concludes that the system was so flawed it only took a day to accumulate enough combustible dust and hydrocarbons in the duct work to overheat, ignite spontaneously, cause an explosion in the rooftop dust collector, and send back a fiery flash that enveloped seven workers.  The CSB found that the ductwork conveyed combustible, condensable vapors above each of three tanks in the mixing room, combining with combustible particles of dust of carbon black and Gilsonite used in the production of black ink.  The closed system air flow was insufficient to keep dust and sludge from accumulating inside the air ducts.  But to make matters worse, the new dust collector design included three vacuuming hoses which were attached to the closed-system ductwork, used to pick up accumulated dust, dirt and other material from the facility’s floor and other level surfaces as a ‘housekeeping’ measure.  The addition of these contaminants to the system ductwork doomed it to be plugged within days of startup.  The report describes a dramatic series of events that took place within minutes on October 9, 2012…

About 1 p.m., an operator was loading a combustible carbon-containing mineral powder, into the bag dump station near the pre-mixing room when he heard what he called a strange, squealing sound.  He checked some gauges in the control room, and as he was leaving he saw a flash fire originating from the bag dump where he had just been working.  He left to notify his supervisor.  At about that same time, other workers heard a loud thump that shook the building.

In response to the flash from the bag dump station and the thump, workers congregated at the entrance to the pre-mix room.  One worker spotted flames coming from one of the tanks.  He obtained a fire extinguisher but before he could use it, he saw an orange fireball erupt and advance toward him.  He squeezed the handle on the extinguisher as he jumped from some stairs, just as the flames engulfed him and six other employees who were standing in the doorway.

The CSB determined that overheating and spontaneous ignition which likely caused the initial flash fire at the bag dump was followed by ignition of accumulated sludge-like material and powdery dust mixture of Gilsonite and carbon black in the duct work above tank 306.  Meantime, the dust collection system, which had not been turned off, continued to move burning material up toward the dust collector on the building’s roof, where a sharp pressure rise indicated an imminent explosion. This was contained by explosion suppression equipment, but the resulting pressure reversed the air flow, back to the pre-mix room, where a second flash fire occurred, engulfing the workers.

The new system was not thoroughly commissioned.  There was no confirmation of whether the system would work as configured, missing opportunities to find potential hazards.  The design flaws were not revealed until the dust explosion.

The report’s safety management analysis points to a lack of oversight by company engineers of the work done by installation contractors. The company chose not to perform a process hazard analysis or management of change analysis – required by company policy for the installation of new processing equipment – because it determined it was merely replacing a previous dust collection system in kind.  However, the new system in fact was of an entirely different design.

Considering the emergency response following the flash fire and dust collector explosion, CSB Investigators found that while workers had received training in emergency response situations, they did not follow those procedures, because U.S. Ink had not developed and implemented an effective hazard communication and response plan.  A fire coordinator was designated to use the public address system to announce a fire and also pull the alarm box. But because the system was not shut down immediately after the first flash fire, he was among the injured and could not perform his duties.

The CSB report notes that the volume of air flow and the air velocity in the company’s dust collection system was significantly below industry recommendations – which, in the absence of a federal combustible dust regulation, are essentially voluntary.  The report states the ductwork design did not comply in several respects with guidelines set by the American Conference of Governmental Industrial Hygienists (ACGIH) Industrial Ventilation Manual.  Nor did the system’s design, the CSB said, comply with the voluntary requirements of NFPA 91, which states: “All ductwork shall be sized to provide the air volume and air velocity necessary to keep the duct interior clean and free of residual material.”

The report cites gaps in New Jersey’s regulatory system, noting the state’s Uniform Construction Code Act has adopted the International Building Code (which references NFPA dust standards) but has also exempted “manufacturing, production and process equipment.”  A proposed CSB recommendation to New Jersey’s Department of Community Affairs calls on the regulatory agency to revise the state’s administrative code to remove this exemption so that dust handling equipment would be designed to meet national fire code requirements.  The state is also urged to implement training for local code officials as local jurisdictions enforce the code, and to promulgate a regulation that requires all occupancies handling hazardous materials to inform the local enforcement agency of any type of construction or installation of equipment at an industrial or manufacturing facility.

CLICK HERE for the full report (pdf)