Connecting a Compressed Gas Cylinder to a “process”

It is pretty standard practice to hook up a compressed gas cylinder to a process.  In fact, many “blanket systems” on a small vessel will use a Nitrogen CG cylinder to provide the blanketing gas.  However, it is even more common to find this setup done improperly.  In this article, I will offer a RAGAGEP to follow that explicitly covers this practice.   First things first, my RAGAGEP states: (emphasis by me)

5.8.2 Check valves

Compressed gas containers should NOT be attached to a process where the container can be contaminated by the backflow of other process materials.

In cases where such a possibility could exist, design consideration shall include the use of check valves and/or traps for this purpose.

These check valves and/or traps shall be checked and maintained on a regular schedule to ensure proper operation.

 

A quick 30-second check can tell us if our connection is protected!  But notice the last sentence/requirement… the check valves and/or traps MUST be in our PM/MI program so that they are checked and maintained on a regular schedule to ensure proper operation.

Of course, it should go without saying that these compressed gas cylinder arrangements will need an MOC and a PSSR; however, this article is to provide some basis for the set-up/design of this connection.  The PSSR should confirm there is a check valve or trap capable of preventing backflow scenarios AND that the device(s) is in the PM/MI program inspection/testing program based on the manufacturer’s recommendations.

For more Compressed Gas Cylinder safety, check out the latest CGA P-1, SAFE HANDLING OF COMPRESSED GASES IN CONTAINERS, 13th edition

 

PLEASE NOTE: this does not apply to Gas Fire Suppression systems like CO2 systems.  This applies ONLY when there is a path for backflow from the process to the cylinder.  NEVER assume the cylinder pressure (always higher than process pressure) as a safeguard.  I know this used to be the fall-back safeguard, but in 2010, the RAGAGEP changed and now requires a check valve or trap.

 

 

 