A manual ΒΌ turn ball valve (#1) was the lead isolation valve in a Double Block and Bleed arrangement. The valve handle was incorrectly secured using a run of pipe BELOW the valve. As shown, the valve handle would swing down in order to OPEN the valve. With the chain securing the valve on the...
Improper isolation of a 1/4 turn ball valve leads to a reportable release of Chlorine