If my bonding/grounding system’s resistance to ground needs to be <10/25 ohms, then why is ESD footwear allowed a resistance of 1,000,000 ohms?

This is another Top 10 question on flammable liquids safety I get from clients, cold calls, referrals, and friends. Most are familiar with the testing limits for path to ground on bonding/grounding stations of 10/25 ohms. In my previous post tonight I explained where these 10 and 25 ohm limits came from and how they

Static electricity from flowing gasoline?

Gasoline (UN1203) is a NON-conductive flammable liquid. These liquids, as all liquids, generate static electricity as they flow through hoses, piping, and free fall into tanks and containers. Since the liquid is non-conductive, it can not conduct the static charge to the hose/pipe/container so the charge can be dissipated to the “ground”. Authorities say quick

Scrubbing the inside of a mix tank with Naptha using a Teflon bristle brush is not advised

Another incident where the lack of respect for static electricity and flammable atmospheres results in severe injuries. A Teflon bristle brush generates a lot of static electricity; coupled with the low flashpoint of Naptha (73F) and we have a serious hazard. At 5:30 a.m. on February 24, 2020, an employee, 42, was scrubbing interior surfaces