Chemical Process Safety (PSM/RMP)

Ammonia released from a cold storage room evaporator

Two persons received minor injuries from exposure to ammonia after a refrigeration system failed and released ammonia that was intended to be contained within the evaporator and refrigeration system. INCIDENT OVERVIEW The evaporator within a refrigeration system of an industrial food processing facility failed and released ammonia in a cold storage room. Two workers suffered

Check valve flange failure leads to Ammonia release (Technical Safety BC)

A safety feature(flanged connection)failure in a refrigeration system released 10 to 20 lbs of ammonia intended to be contained. The ammonia refrigeration system is designed to operate at 250 Psig. The system uses welded or flanged connections to connect components such as compressors, condensers, evaporators, and liquid receivers. Piping and fittings including flanges, different types

Determining frequency of emergency coordination activities (changes to response capabilities)

Today, the EPA’s RMP Info Center published the following guidance on the REVISED emergency coordination activities in the RMP Rule.  The Risk Management Program regulations require owners and operators of stationary sources to coordinate their response needs ANNUALLY, or more frequently if necessary, with local emergency planning and response organizations (40 CFR §68.93(a)). Are stationary

Face Coverings, flame-retardant/resistant clothing (FRC) and hazardous locations

UPDATED 6/4/2020 with an FR face-covering item. (NOT an endorsement!) Westex UltraSoft® FR Face Mask 7oz. Westex UltraSoft® 88% Cotton / 12% High Tenacity Nylon Sizes: Regular Colors: Orange (OR) Style: FR9805 Source: https://rascofr.com/product-category/face-covering/ Last week the good folks are DuPont opened a can of proverbial worms that about a dozen of us have been

Requirements for when rooms or buildings exceed the maximum allowable quantity per control area for flammable liquids

5705.3.7 Rooms or buildings for quantities exceeding the maximum allowable quantity per control area.Where required by Section 5705.3.5.3 or 5705.3.6.1, rooms or buildings used for the use, dispensing, or mixing of flammable and combustible liquids in quantities exceeding the maximum allowable quantity per control area shall be in accordance with Sections 5705.3.7.1 through 5705.3.7.6.3.