Chemical Process Safety (PSM/RMP)

Bonnet gasket leaking from chiller isolation valve to oil pot (10 pound release)

Incident overview The bonnet gasket on the isolation valve between the brine chiller and the oil pot leaked approximately 10 lbs ammonia into the mechanical room. Two (2) refrigeration technicians had completed draining oil from the oil pot and when the isolation valve was closed the bonnet gasket leaked ammonia into the brine chiller insulation.

Guidelines for Ammonia Refrigeration Plant Equipment Integrity Programs (TSBC Draft #2)

Following the release of the Fernie Incident Investigation Report Technical Safety BC developed new ammonia refrigeration industry maintenance guidelines to support facility owners and refrigeration professionals with implementing the report recommendations. The purpose of these guidelines is to provide ammonia refrigeration plant owners and operators with guidance and basic information about the development, documentation, and

Anhydrous Ammonia Tank Failure – South Africa 1973, Detailed report on a major disaster in a fertilizer plant

On July 13, 1973, at a fertilizer plant, one of four 50-ton (metric) pressure-storage tanks (horizontal bullet type) failed. The failure resulted from brittle fracture of a dished end. No specific source of cracking, or a “triggering incident” was identified. An estimated 30 ton of anhydrous ammonia was released, plus another 8 ton from a

Line Break gone BAD (Phosgene)

At 2:30 p.m. on September 13, 2010, Employee #1, Employee #2, and Employee #3 were tasked with the dismantling of a scaffold level within a phosgene containment dome. During their dismantling work, at approximately 80 feet above the ground, alarms specific to phosgene gas were triggered. The process within this Dome was the manufacturing and

What RMP information will be available to the public under the new RMP Reconsideration Final Rule

Under the final RMP Reconsideration rule, members of the public can continue to obtain access to RMPs through three different means: Read-only access to the full version of facility RMPs at reading rooms by appearing in person at a Federal reading room; Read-only RMP access directly from the local emergency planning committee in the location

RMP Reconsideration Final Rule is FINAL as of November 20, 2019

On November 20, 2019, EPA finalized changes to the Risk Management Program (RMP) Reconsideration final rule to better address potential security risks, regulatory consistency and reasonable consideration of costs. The changes are intended to promote better emergency planning and public information about accidents and maintain the trend of fewer significant accidents involving chemicals regulated under

Another CATASTROPHIC FAILURE of a Ammonia Refrigeration vessel (150-gallon Vessel @ chicken slaughterhouse)

We have had another catastrophic failure of a pressure vessel used in an ammonia refrigeration process and this time we caught it on camera.  The event occurred last week and unfortunately, I have not heard of any causes or if anything special was happening within the process when this failure occurred.  This picture shows us